Powering a 347 Volt SOX ballast (2)

Powering a 347 Volt SOX ballast (2)

Click to view full size image

Using 120v 60Hz on a 350 watt PSMH multi-tap ballast, with everything else capped, including the ignitor tap and lamp out but leaving the capacitor as wired, I simply connected the 347 volt tap of the PSMH (& 2nd COM) to the 347 volt LPS ballast still mounted on the Alpha 4. 135w lamp lights up normally to full power.

IMG_96642BIMG_9666.jpg IMG_3202.jpg IMG_3613.jpg IMG_36202BIMG_3616.jpg

Light Information

Light Information

Manufacturer:Sola Canada
Model Reference:75-17-1419
Lamp
Lamp Type:SOX
Fixture
Fixture Type:Alpha 4 luminaire
Ballast Type:magnetic auto-lag L73/L74
Electrical
Wattage:135 watts (lamp), 180w consumption
Voltage:347 V only

File information

File information

Download: Download this File
Filename:IMG_3613.jpg
Album name:lights*plus / SOX or LPS testing
Keywords:Gear
File Size:1493 KB
Date added:Nov 10, 2019
Dimensions:2000 x 1333 pixels
Displayed:134 times
URL:https://www.lighting-gallery.net/gallery/displayimage.php?pos=-167263
Favorites:Add to Favorites
Comments
Fluorescent05
Sr. Member
****
Offline

Gender: Male
View Posts
View Gallery

Zack


View Profile Offline
Nov 10, 2019 at 02:24 PM Author: Fluorescent05
Nice! Are you going to put it into service like this?

I can't pretend a stranger is a long awaited friend. -Neal Peart

lights*plus
Sr. Member
****
Offline

Gender: Male
View Posts
View Gallery

George Liv Photo


GoL george.liv.37 UC_OfF2pa6aOcXLAut16jw9g
View Profile WWW Offline
Nov 10, 2019 at 02:28 PM Author: lights*plus
I'm going to sell the Alpha 4s without the L73/L74 ballast. I could also trade a few here on LG.

Will also sell the 347v ballast by itself with these directions (how to power it with 120volts).
Alights
Full Member
***
Offline

View Posts
View Gallery

USA (120V 60HZ)


View Profile Offline
Nov 10, 2019 at 02:54 PM Author: Alights
I've done this with ballasts, you don't even need the cap
ramdude2014
Jr. Member
**
Offline

Gender: Male
View Posts
View Gallery


View Profile Offline
Nov 10, 2019 at 05:55 PM Author: ramdude2014
How do I wire a ballast to power a 240 volt ballast?

Next stop gate T17!

Fluorescent05
Sr. Member
****
Offline

Gender: Male
View Posts
View Gallery

Zack


View Profile Offline
Nov 10, 2019 at 06:34 PM Author: Fluorescent05

How do I wire a ballast to power a 240 volt ballast?

Use a multitap ballast and wire the 120v to your 120v input, the 240v of the multitap ballast to the ballast you want to power, and don't forget to cap up the lamp lead of the ballast being used as a step-up transformer.

I can't pretend a stranger is a long awaited friend. -Neal Peart

lights*plus
Sr. Member
****
Offline

Gender: Male
View Posts
View Gallery

George Liv Photo


GoL george.liv.37 UC_OfF2pa6aOcXLAut16jw9g
View Profile WWW Offline
Nov 10, 2019 at 06:38 PM Author: lights*plus
Use a multi-tap ballast with one tap being 240 volts, and with higher watts than your 240v ballast.

Just wire the HPS, M-H or MV multi-tap ballast with 120v and use the 240 volt tap to power your 240v ballast.

You might also be able to use the 277volt tap but the output might be too high. In this case I'd use a multi-tap ballast equal to or slightly less watts than what you want to power.
Fluorescent05
Sr. Member
****
Offline

Gender: Male
View Posts
View Gallery

Zack


View Profile Offline
Nov 10, 2019 at 06:41 PM Author: Fluorescent05
Oh yeah I forgot about the higher wattage thing.

I can't pretend a stranger is a long awaited friend. -Neal Peart

ramdude2014
Jr. Member
**
Offline

Gender: Male
View Posts
View Gallery


View Profile Offline
Nov 10, 2019 at 06:57 PM Author: ramdude2014
So I can use my multi tap 1000 watt halide to power my 400 watt 240 volt ballast but how do I get 2 hots for the 240 volt?

Next stop gate T17!

lights*plus
Sr. Member
****
Offline

Gender: Male
View Posts
View Gallery

George Liv Photo


GoL george.liv.37 UC_OfF2pa6aOcXLAut16jw9g
View Profile WWW Offline
Nov 10, 2019 at 07:12 PM Author: lights*plus
You mean +120v & -120V? What sort of 240V ballast are we talking about here?

All multi-tap ballasts typically have 2 COM wires (wired just under the covers)... From your wall use 120v & COM. To your ballast you need to power up, use the 240v tap & the other COM. You can wire all COMs together if you only have one.
ramdude2014
Jr. Member
**
Offline

Gender: Male
View Posts
View Gallery


View Profile Offline
Nov 10, 2019 at 07:34 PM Author: ramdude2014
I was under the impression that a 240 volt only ballast I would use the 240 volt input and the com. As the other hot! And then have only an earth ground.. like a 240 volt water heater

Next stop gate T17!

lights*plus
Sr. Member
****
Offline

Gender: Male
View Posts
View Gallery

George Liv Photo


GoL george.liv.37 UC_OfF2pa6aOcXLAut16jw9g
View Profile WWW Offline
Nov 10, 2019 at 07:46 PM Author: lights*plus
No (I think). You have 2 ballasts. You exploit your 1KW ballast with 6 connections (ground included)!

Connect from your wall outlet to the 120v & com of your 1KW ballast.
Connect your 400w ballast to the 240v tap & com of your 1KW ballast.
2 more connections for earthing onto the core of the 1kw ballast. Done.
rjluna2
Sr. Member
****
Offline

Gender: Male
View Posts
View Gallery

Robert


GoL
View Profile Offline
Nov 12, 2019 at 07:16 AM Author: rjluna2
That's explains why you have to convert the proper voltage for this LPS ballast

Pretty, please no more Chinese failure.

Men of God
Full Member
***
Offline

Gender: Male
View Posts
View Gallery


jiachao.wei.71 chao_813975447 UChyTpXvlQ8ZCfBPP_lJjubg chao990613
View Profile Offline
Aug 28, 2020 at 07:15 AM Author: Men of God
这好像有点欠压

我不会英文,所以我用中文,请你们用翻译网站翻译我打的字!

I can't in English, so I in Chinese, please use the translation website to translate my words!

Men of God
Full Member
***
Offline

Gender: Male
View Posts
View Gallery


jiachao.wei.71 chao_813975447 UChyTpXvlQ8ZCfBPP_lJjubg chao990613
View Profile Offline
Aug 28, 2020 at 07:15 AM Author: Men of God
这好像有点欠压

我不会英文,所以我用中文,请你们用翻译网站翻译我打的字!

I can't in English, so I in Chinese, please use the translation website to translate my words!

joseph_125
Hero Member
*****
Offline

Gender: Male
View Posts
View Gallery


GoL
View Profile Offline
Aug 28, 2020 at 09:05 PM Author: joseph_125
This trick is often used on factory wired HID fixtures designed for higher voltages to power the 120v halogen restrike lamp too. In fact some ballasts will mention this on the label.